REACH | RoHS | CE | CPR
Application
The cables are suitable for power and lighting circuits and building wiring suitable
for use in semi flush exposed conduits, embedded
conduits and in closed
installation ducts. Ideal for internal wiring of appliance.
Standard
EN
50363-3 with BS 7655-4.2 (Only for sheath).
Technical Data
Voltage Rating : 1.5 mmsquare to 35 mmsquare - 300 /
500V
Temperature Range : -15°C to 70 °C
Minimum
Bending Radius
Upto 10 mm2 : 10 X Overall Diameter.
16 & 35
mm2 : 12 X Overall Diameter.
16 & 35 mm2 : 12 X Overall
Diameter.
Test Voltage : 2 kV for 15 min
Cable Construction
Conductor :
Plain annealed copper conductor : 1.5 & 2.5 mm2
Class -1, 4.0 to 35 mm2 stranded Class 2 complying with BS EN 60228, HD 383, IEC
60228.
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1
complying with EN 50363-3
Sheath : PVC (Polyvinyl Chloride )
compound type Type 6 complying with BS 7655-4.2
Insulation Colours
: Blue and brown
Sheath Colour : Grey RAL 7001
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 - blue, 09 - brown
Part Number | Nominal Cross Sectional Area (Sq. mm) | Nominal Insulation Thickness (mm) | Nominal Sheath Thickness (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approx. Net Weight (kg/km) |
---|---|---|---|---|---|---|
01150101xx10 | 1.5 | 0.70 | 0.8 | 4.20 | 5.00 | 37 |
01150102xx10 | 2.5 | 0.80 | 0.8 | 4.80 | 5.70 | 51 |
01150103xx10 | 4 | 0.80 | 0.9 | 5.50 | 6.70 | 75 |
01150104xx10 | 6 | 0.80 | 0.9 | 6.00 | 7.30 | 98 |
01150105xx10 | 10 | 1.00 | 0.9 | 7.30 | 8.80 | 152 |
01150106xx10 | 16 | 1.00 | 1.0 | 8.40 | 10.10 | 220 |
01150107xx10 | 25 | 1.20 | 1.1 | 10.00 | 12.10 | 336 |
01150108xx10 | 35 | 1.20 | 1.1 | 11.10 | 13.50 | 353 |
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown.