REACH | RoHS | CE | CPR
Description
India’s 1st Heat Resistant and Flame Retardant REACH and RoHS Compliant Cable with Unilay Conductor. No Loose Contacts, No Broken Ends | No Sparking and Overheating.
- REACH, ROHS, CE and CPR Compliant
- Anti-Rodent, Anti-Termite
- 100% Electrolytic Copper
- More than 101% Conductivity
Application
Suitable for use in conduit and for fixed, protected installation, ideal for high density wiring.
Technical Data
Approvals : IS 694 marked, FIA /
TAC
Voltage Grade : Up to and including
1100V
Conductor : Thin strands of electrolytic
copper are multi-drawn for uniformity of resistance, dimension and flexibility. The
drawn strands are uni-laid with high precision and compacted. Thus forming a
perfectly circular conductor which enables reduction in overall diameter for space
saving in high density wiring.
Conductor Speciality
: The strands do not get cut when stripping the
insulation. The conductor offers perfect contact at pins, terminals and sockets.
Thus, eliminating spot heating and sparking.
Insulation
: Specially formulated heat resistant & flame
retardant PVC insulation is used. The HR FR property retards the propagation of
flame without compromising safety.
Insulation Conformity
: IS 5831, Type C - HR 85°C +
FR
Colours : Green, Black, Red, Yellow, Blue,
Grey, White
Marking : The cables are printed
with marking of "RR-UNILAY HR FR’
Packing : 90
mtr. coils packed in protective cartons
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of
‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 –
yellow, 06 – grey, 07 – white.
Part Number | Nominal Cross Sectional Area (Sq. mm) | Nominal Insulation Thickness (mm) | Number *Nominal Dia. of Strands | Approx. Overall Diameter (mm) | Max. DC Conductor Resistance at 20°C (Ω/km) | Current Rating (Amps) | |
---|---|---|---|---|---|---|---|
Casing | Concealed | ||||||
01030101xx40 | 1 | 0.7 | 37/0.20 | 2.6 | 19.5 | 14 | 13 |
01030102xx40 | 1.5 | 0.7 | 37/0.22 | 3.0 | 13.3 | 18 | 16 |
01030103xx40 | 2.5 | 0.8 | 61/0.22 | 3.6 | 7.98 | 24 | 20 |
01030104xx40 | 4 | 0.8 | 61/0.30 | 4.1 | 4.95 | 32 | 26 |
01030105xx40 | 6.0 | 0.8 | 91/0.29 | 4.6 | 3.30 | 38 | 33 |
*Conductor as per IS 8130
Properties
Test | Test Method | Values |
---|---|---|
Limited Oxygen Index | IS 10810 P-58 | > 29% |
Limited Temp. Index | IS 10810 P-64 | >250 °C |